_______________________________________________________________________________________ Below is a list of the meter Firmware changes for the ZAPTRONIX Meters _______________________________________________________________________________________ To determine the Firmware Version of the of the meter. The startup display should be programed to display Firmware Revision (on by default). When the meter is powered up "VER ?.?" will be seen _______________________________________________________________________________________ ZAP03BE 230/110V Demand TOU meter Ver 2.? Any Version less than 3.0 are sample meters and should not be used for billing purposes Ver 3.0 1st release Ver 3.1 Not released Ver 3.2 1) Updated spurious Maximum Demand Resets if meter set to External EOB pulse when the meter powers up 2) Thermal Demand is now cleared on powerup 3) Thermal Demand calculations do not reset on Max Demand Reset 4) Thermal Demands Absolute calculation updated to calculate if meter CT reversed 5) Counter Icons (kwh) removed from display 6) Display CTVT ratio updated Ver 3.3 1) Minor Communications update Ver 3.5 1) Added Per Phase Logging Ver 3.6 1) Fixed display scroll button Ver 3.7 1) Meter delay removed before next signon after break command 2) When meter is in auto scroll, will now scroll manually Ver 3.8 1) Time meter has been on register since last MDR fixed Ver 3.9 1) Passwords updated for logging and LM registers 2) Modbus Beta implemented 3) Datalogging dump speedup by allowing binary data dump Ver 4.0 1) 1st Modbus release Ver 4.2 1) LM meter has operate modem on flag port (fixed baud) 2) Fixed bug from 4.1 that stopped Ext MDR EOB pulse Ver 4.3 1) Added logging for counter inputs _____________________________________________________________________________________ ZAP03LM 230/110V Load managment,Demand, TOU meter Ver 3.0-3.1 These are sample meters and should not be used for billing purposes Ver 3.2 1) Load Managment relays set (on) on powerup 2) Updated thermal Load management relay hysteresis calcs 3) Load Managment relay status logging added Ver 3.3 1) Minor Communications update Ver 3.4 1) Fixed LM override limit so that relays drop out within 10sec Ver 3.5 1) Added Per Phase Logging Ver 3.6 > 1) As Per ZAP03BE _____________________________________________________________________________________ The Firmware of the meter can be updated. Please contact Zaptronix for details on Updating meter Firmware.