ZAP03BEZAP03BE

ENERGY DEMAND LOGGING MULTI-TARRIF METER

Adobe Acrobat (PDF) Download Brochure  |  Adobe Acrobat (PDF) Download Manual

Quick feature guide

  • 4 Quadrant, billing meter for active (Wh) and reactive energy (VArh) demand (VA)
  • 3 Phase , CT and VT connected meter
  • Class-1 accuracy
  • Flexible multi-tariff time of use (TOU) billing meter with monthly auto registration
  • Extensive 4 channel data logging from 18 readings and event recording
  • Remote automated meter reading ready through configurable IO
  • Large, scrolling LC-Display which replaces instrumentation meters
  • Certified compliance with standards: IEC 62053-21, IEC 62053-23, (SABS) and OFGEM (UK)
  • Manufactured under ISO 9001:2000 quality standards
  • Engineering software included / available for download at no charge

MODEL CONFIGURATION OPTIONS

ZAP03BE240V5A4w

3 Phase, 4-wire, 230V, 5A, CT

ZAP03BE110V5A3w

3 Phase, 3-wire, 110V, 5A, VT & CT

ELECTRICAL RATING

Standard

IEC62053-21,IEC62053-23

ZAP03BE 230V Voltage range (P-N)

184 – 275 V

ZAP03BE110V Voltage range (P-P)

88 – 132 V

Frequency Range

40 – 60 Hz

Burden Voltage circuit< 1.0W / 2.0VA ; Current circuit< 1.0 VA

Operating temperatures

0 ºC to + 45 ºC

Accuracy class 1

Protection class 2

Supports VT & CT connections with compensation factor

One ZAP03BE per CT set since S2 is internally common to neutral

DISPLAY

Instrumentation values (see instrumentation data)

Real time quadrant indicator ANSI or IEC

Power fail indicator

Large 8-digit with (auto) configurable decimal point & multiplier

Digit height 9 x 4.5mm

Life in excess of 10 years

COMMUNICATIONS

Standard IEC 62056-21 flag port 9600 bps

Serial RS232 port with modem handshaking / GSM or PSTN

RS232 to RS485 via converter (optional)

INPUTS & OUTPUTS

10 way connector: 4 outputs, 2 inputs, 2 ground & 5Vdc 100mA max. auxiliary power supply with 6kV isolation & own ground

Serial Interface uses 1 output , 1 input

Modem Interface uses 2 outputs, 2 inputs

4 pulse outputs can be programmed to:
Active import, export, ABS -energy (kWh),Reactive import, export, ABS -energy (kVAr), Apparent energy (kVA) for pulse output verification. End of integration period or maximum demand reset

Inputs can be used for: Pulse counters, end of billing period & external maximum demand reset

Pulse type
Maximum Rating
Pulse width
End of demand period

Specification
30Vdc, 10 mA
0.5 – 10 s (0.5 s steps)
10 – 100 ms (10 ms steps)

Pulse output verification is to IEC62053-31 standard

LED outputs for active & reactive energy IEC62053-31

Push buttons for display & protected programming

SECURITY (PHYSICAL & DATA)

3 -level access password: full, read & limited write, read only

All meter setup parameters can be done amass from a template

Meter functions with any phase & neutral connected

User access tracking: date & time, count & serial number

Programming protection: sealed push button & password

Factory sealed case. Sealable terminal cover

On power down capacitor & battery allows for data backup & continued RTC operation

EVENT LOGGING

All events are date & time stamped

Operational events

Last maximum demand reset, user access power fail, power restored

Hardware events

RTC fail, Backup battery fail

Tamper, installation & quality of supply events

Phase missing or out of sequence

Power on duration

BILLING REGISTRATION

Active energy (kWh)

Import & Export per phase & total

Reactive energy (kVarh)

Import & Export per phase & total

Maximum demand modes

Block, Sliding window & Thermal mode

Maximum of

Active (kW) & Apparent power (kVA)

Demand cycles

2,3,4,5,10,15,20,30 60minutes

Trigger

Button reset, external or auto RTC

Automated registering & history

Last 3 periods plus present of energy & maximum demand for 4 tariffs

Time of use (TOU)

Flexible control for billing quantities

2 Counters (pulse)

For externally metered gas, water etc.

INSTRUMENTATION METERING

Instrumentation values read via optical port, RS485 or LCD

Voltage (V), Current (A), Frequency (Hz) & Power factor per phase. Total current (A), Active (kW), Reactive (kVArh), Apparent (kVA)

TIME OF USE (TOU) CONTROL

DST –Day Light Savings Time Support

Active & future TOU table with changeover date

Switching by internal real time clock

4 rates with 2 banks & 4 seasons all configurable

8 daily time schedules each selecting 4 rates with 96 intervals

16 Public holidays, recurring & not with configurable schedule

Two different weekend days

DATA LOGGING

4 data logging channels can log any of 18 metered values in 1,2,3,4,5,10,15,20,30 or 60 minute intervals

kWh (import, export), kVArh (import, export), kVAr (import, export), kW (import, export), Wh (ABS, phase 1,2,3) W (ABS,phase 1,2,3), pulse counters 1,2

Memory non-volatile flash memory

Capacity depends on frequency & number of channels recorded (4 channels logged every 30 min will record 63 days)

ACCESSORIES

Opto-coupler for flag port with magnetic base (USB) & (RS232)

ZP0067 coverts 8pin connector to RS485

RemIt!Lite software download

Configure & read meter data

GSM-Data Call modem kit

For GSM data call functionality

CASE AND DIMENSIONS

Dimensions

110 x 120 x 75 mm

Case dimension standard

BS5685 & DIN rail mountable

Weight

585g

Markings are in accordance with IEC1036

Property ownership marking (optional)
Meter serial number & connection diagrams part of case markings

Terminal Diameter

4.5 mm

Terminal Cover

Transparent & sealable