ZAP03DSZAP03DS

THREE PHASE ACTIVE (Wh) ENERGY METER

Adobe Acrobat (PDF) Download Brochure  |  Adobe Acrobat (PDF) Download Manual

Quick feature guide

  • Billing meter for active energy (wH)
  • 3 Phase , CT and VT connected meter
  • Class-1 accuracy (exceeds 0.5%)
  • Large, multi function LC-Display
  • Standard 7 module DIN size
  • On site setup and data communication via flag port
  • Certified compliance with standards: IEC 62053-21
  • Manufactured under ISO 9001:2000 quality standards
  • Engineering software included / available for download at no charge

CONFIGURATION OPTIONS

ZAP03DS230V5A4w

3 phase, 4-wire, 230V, 5A, CT

ELECTRICAL RATING

Standards

IEC62053-21

ZAP03DS230V Voltage Range (P-N)

155 – 275 V

Frequency Range

40 – 60 Hz

Burden voltage circuit <0.37W, current circuit <1.0VA

Operating temperatures

-10 ºC to + 55 ºC

Accuracy Class 1

Protection Class 2

Supports CT connections

One ZAP03DS per CT set since S2 is internally common to neutral. Terminals 1, 4, 7, 11 are common.

DISPLAY

Large 8-digit, 9.0 x 4.5 mm digit size

Configurable scroll delay & decimal point (0-3) & k or M multiplier

Energy (kWh) (import, export, ABS or total).

Instantaneous Quadrant display: IEC or ANSI

Life in excess of 10 years, easily replaceable

COMMUNICATIONS

Standard IEC 62056-21 flag port

INPUTS & OUTPUTS

2 sets: import & export energy

Potential free opto-isolated, Vmax 30 Vdc, Imax 20 mA, pulse rate & duration configurable

Pulse output verification to IEC62053-31 standard

LED outputs for active energy IEC62053-31

SECURITY (INSTALLATION & DATA)

Programming protection password

Factory sealed case

Upon power down a super capacitor, battery & backup battery ensures backup & continued RTC operation

Self diagnosis, reverse polarity & incorrect phase sequence detection

BILLING METERING

Active energy (kWh)

Import & Export & Total

ACCESSORIES

Optical Coupler for flag port with magnetic base (USB)

Metal clip for magnetic base

RemIt!Lite software download

Configure & read meter data

CASE AND DIMENSIONS

Dimensions

110x 122.5 x 66 mm (U7 DIN)

Terminal diameter

4.5 mm

Weight

<450 g

Property ownership marking (optional)
Meter serial number and connection diagrams part of case markings