ZAP(pi) 3AM+ZAPp 3AM+

ENERGY DEMAND LOGGING MULTI-TARRIF METER

Adobe Acrobat (PDF) Download Brochure  |  Adobe Acrobat (PDF) Download Manual

Quick feature guide

  • Billing meter for active (Wh) and reactive (VArh) energy demand (VA)
  • 3 Phase , CT or high load current direct connect meter configuration
  • Class-1 accuracy
  • Flexible multi-tariff (TOU) billing meter with auto registration
  • Profile logging of total energy and average energy demand
  • Remote automated meter reading ready
  • Large, multi function, backlight, LC-Display with IEC 62056-61 OBIS code
  • Replaces need for instrumentation meters with scrolling display
  • Certified compliance with standards: IEC 62053-21, IEC62053-23
  • Manufactured under ISO 9001:2000 quality standards
  • Engineering software included / available for download at no charge

CONFIGURATION OPTIONS

ZAPπ3AM240V5A4w

3 phase, 4-wire, 240V, 5A, CT

ZAPπ3AM240V100A4w

3 phase, 4-wire, 240V, 100A, inline

ZAPπ3AM240V160A4w

3 phase, 4-wire, 240V, 160A, inline

ELECTRICAL RATING

Standards

IEC62053-21, IEC62053-23

ZAPπ3AM240V Voltage Range (P-N / P-P)

57.7/100 – 230 /400 V

Frequency Range

40 – 60 Hz

Burden voltage circuit <1W, current circuit <0.05VA

Operating temperatures

-30 ºC to + 70 ºC

Storage temperatures

-45 ºC to + 85 ºC

Accurancy Class 1

Protection Class 2

Supports CT connections

Multipule meter can be installated (4 ZAPπ per set of CTs)

DISPLAY

Instrumentation values (see section) auto & keystroke scrolled

Large 8-digit with backlight with icons for import, export, comms etc.

IEC 62056-61 OBIS code display with digit height 11.9mm

Life in excess of 15 years

COMMUNICATIONS

Standard IEC 62056-21 flag port

Serial RS485 port

INPUTS & OUTPUTS

4 pulse outputs: Active import (kWh) export energy, Reactive import (kVAr) export energy

Two energy verification outputs: Active (Wh) & Reactive (VArh)

1 Hz pulse output

Pulse output verification to IEC62053-31 standard

RS485

LED outputs for active & reactive energy IEC62053-31

Push buttons for display and protected programming

SECURITY (PHYSICAL & DATA)

User access tracking: date & time and count

Programming protection: sealed push button and password

Factory sealed case. Sealable terminal cover by owner

For power down a super capacitor, battery & backup battery ensures backup & continued RTC operation

Reverse current warning & neutral loose or disconnect warning

EVENT LOGGING

Operational Events

Last maximum demand reset & programming time

Hardware Events

Status for Battery Voltage, Memory, Meter Errors

Tamper or supply failure

Terminal cover open, per phase failure, power fail, power restore

Quality of supply

Voltage over & under record (user selectable thresholds)

BILLING METERING

Active energy (kWh)

Import & Export

Reactive energy (kVarh)

Import & Export

Maximum demand modes

Block and Sliding / Rolling mode

Demand cycles

5, 10, 15, 30 or 60 minutes

Rolling interval

1, 2, 3 or 5 minutes

Registration

Button set, or auto RTC

Automated registering & history

Last 15 periods of energy & maximum demand for 4 tariffs

Time of use (TOU)

Flexible control of the billing quantities for TOU

INSTRUMENTATION METERING

LCD

Voltage, Current & power factor per phase

LCD

Active (kW), Reactive (kVAr), Apparent (kVA)

TIME OF USE (TOU) CONTROL

Switching by internal real time clock

4 seasons, configurable

10 daily time sections each selecting 4 tariffs

Public holidays & weekend days included

PROFILE LOGGING

2 data logging channels can log Average Active Power of demand cycle & Active Import Energy
in 10, 20, 30 or 60 minute intervals

Non volatile flash memory

Capacity: 20 min logging will record 165 days

ACCESSORIES

Optical Coupler for flag port with magnetic base (USB)

PR510 programmer and reader used with MPS software

EDAT+g for GSM/GPRS AMR at multi meter (128) installations

EDAT+e for Internet AMR at multi meter (128) installations

Meter Programming Software MPS

Meter reading & configuration software –download for free

CASE AND DIMENSIONS

Material

Reinforced Clear Polycarbonate

Dimensions

263 x 175 x 83 mm

Weight

<1.5 kg , depends on configuration

Ingress rating

IP60

Markings are in accordance with IEC1036

Property ownership marking (optional)
Meter serial number & connection diagrams part of case markings